ShTT-0.95 Current Transformer
The ShTT-0.95 current measurement transformers are designed for use in circuits for commercial and technical electricity metering in electrical networks with a nominal voltage up to 0.95 kV.
Design Features
Transformer Design
The ShTT-0.95 current transformer was specifically developed to simplify and accelerate installation in switchgear of various types and technical conditions.
Transformer Secondary Circuits
The ShTT-0.95 current transformer features factory-ready secondary circuits (custom length up to 5 meters). The secondary circuit cable is an integral part of the transformer’s construction and does not require additional connections or sealing on the transformer side. The secondary circuit is terminated with U-shaped cable lugs (optional upon order), simplifying connection to the electricity meter or test terminal block (TTB).
Mounting on Electrical Busbar
Technical Specifications
| Current Transformer Characteristics | |
|---|---|
| Maximum nominal/operating voltage, kV | 0.95 / 1.0 |
| Number of secondary windings | 1 |
| Nominal primary current Inom, A | 150, 200, 250, 300, 400, 500, 600 |
| Nominal secondary current, A | 5 |
| Accuracy class per GOST 7746 | 0.5S |
| Nominal safety factor of secondary winding, Kb nom | 10 |
| Thermal withstand current (1 sec.), A | 60· Inom |
| Cross-section of secondary cable cores, mm² (for standard secondary circuit lengths) | 2.5 |
| Standard secondary cable lengths, m (other lengths agreed with manufacturer) | 0.5 / 2.0 / 4.0 / 5.0 |
| Nominal secondary load at cos φ = 1, VA* (for corresponding secondary cable length) | 2.5 / 2.0 / 1.0 / 1.0 |
* – nominal secondary load at the end of the secondary circuit cable is indicated.
Dimensions (mm)
Compliance with Regulatory Requirements
The ShTT-0.95 current transformers are entered into the State Register of Measuring Instruments (GRSI) under number 57345-14. Calibration interval – 8 years.
The current measurement transformers comply with the requirements of GOST 7746 and TR TS 004/2011.
Application Experience of ShTT-0.95
Installation experience with the ShTT-0.95 has shown that its use reduces the time and quantity of materials required by more than half. The greatest benefit is achieved in old switchgear (minimizing the number of affected switchgear components) or in switchgear with installation space limitations for transformers (due to the transformer’s compactness and mounting method, numerous additional possibilities for its installation arise).
Order Specification
ShTT – 0.95-I-[AAA]/5-0.5S-[L]-[M]
[AAA] – primary current in A: 150, 200, 250, 300, 400, 500, 600;
[L] – length of pre-terminated secondary circuits in m.;
[M] – accessories:
V – mounting on a bushing (the kit includes an internal bushing and a fastener)
Packaging
The standard packaging is a cardboard box for 9 transformers of the same type, with mounting accessories and datasheets.
Alternative packaging forms or sets are agreed upon when ordering.